Electrical

Indonesian Color Coding

Cable

Old (PUIL 2000)

New (PUIL 2011)

Phase 1 (R)

Red

Black

Phase 2 (S)

Yellow

Brown

Phase 3 (T)

Black

Gray

Neutral

Blue

Blue

Ground

Green-Yellow

Green-Yellow

For 1 phase use Red, Yellow, Black, Brown or Gray for phase.

Cable Diameter

Diameter (mm)

Max Current (A)

0.75

12

1

15

1.5

18

2.5

26

4

34

6

44

10

61

16

82

25

108

35

135

50

168

70

207

95

250

120

292